NAVAIR       INTERNATIONAL LIMITED............    LEADERS IN THE FIELD OF PASSIVE FIRE PRODUCTS.
SPECIFICATION

GENERAL CONSTRUCTION 

Fire rated wooden doors shutters are made of two non-combustible boards sandwiching high-grade proprietary insulation material and intumescent compounds with teak wood edging all around the shutter. An intumescent fire sealing smoke strip is incorporated in the edging of shutters and in frames on all sides except bottom. These are faced with commercial/teak plywood to provide aesthetic finish. Both single leaf and double leaf doors in all sizes are available.

We recommend the use of VIPER FR-880 fire retardant primer and VIPER FRS -881 as the finishing fire retardant Enamel paint for the door, which makes the surface of the fire doors flame proof.

SPECIFICATIONS OF 30 MINUTES RATED FULLY INSULATED WOODEN FIRE AND SMOKE CHECK DOOR - PRODUCT CODE WDF 8101

PARTICULARS

Providing and fixing doorframe of Seasoned hardwood / 2nd class Teakwood/ Pressed steel frame * of 120mm * 70mm section (nominal) with heat activated Intumescent fire seal strips of min 12mm * 4mm (for smoke sealing) fixed on all the three sides except the bottom. The frame being suitable for mounting 30 minutes fire resistant shutters, with one coat of anti-termite fire retardant primer. 

Providing and fixing of non-metallic, 45mm thick, asbestos free, FULLY INSULATED composite Fire & Smoke check shutters of 30 minutes fire resistance rating confirming to BS: 476 part-22, IS: 3614 part II, as per prototype tested & Certified at CBRI Roorkee, duly approved by TAC (Traffic Advisory Committee) suitable for mounting on door frames as per item no.1. It comprises of two non combustible boards each 12 mm thick, sandwiching 20 mm thick Fire Resistant Filler, faced with 3mm commercial ply facing on both faces and teakwood lipping all around the shutters with heat activated Intumescent Fire Seal strip of size 12 mm * 4mm mounted in the grooves in the shutter on all sides except bottom with hinges and one coat of Anti-termite fire retardant primer.

-- SINGLE LEAF                                                                      Rs. Per Sq. Mtr.

-- DOUBLE LEAF                                                                    Rs. Per Sq. Mtr.

FINISHING: Painting the shutters with fire retardant paint of “VIPER” Brand to provide Class-1 surface spread of flame conforming to BS: 476 Part-7, IS: 12777 is desired shade including cleaning and preparation of surface.

SPECIFICATIONS OF 60 MINUTES RATED FULLY INSULATED WOODEN FIRE AND SMOKE CHECK DOOR - PRODUCT CODE WDF 8102

PARTICULARS

Providing and fixing doorframe of Seasoned hardwood / 2nd class Teakwood/ Pressed steel frame * of 120mm * 70mm section (nominal) with heat activated Intumescent fire seal strips of min 12mm * 4mm (for smoke sealing) fixed on all the three sides except the bottom. The frame being suitable for mounting 60 minutes fire resistant shutters, with one coat of anti-termite fire retardant primer. 

Providing and fixing of non-metallic, 50mm thick, asbestos free, FULLY INSULATED composite Fire & Smoke check shutters of 60 minutes fire resistance rating confirming to BS: 476 part-22, IS: 3614 part II, as per prototype tested & Certified at CBRI Roorkee, duly approved by TAC (Traffic Advisory Committee) suitable for mounting on door frames as per item no.1. It comprises of two non combustible boards each 12 mm thick, sandwiching 20 mm thick Fire Resistant Filler, faced with 3mm commercial ply facing on both faces and teakwood lipping all around the shutters with heat activated Intumescent Fire Seal strip of size 12 mm * 4mm mounted in the grooves in the shutter on all sides except bottom with hinges and one coat of Anti-termite fire retardant primer.

-- SINGLE LEAF                                                                      Rs. Per Sq. Mtr.

-- DOUBLE LEAF                                                                    Rs. Per Sq. Mtr.

FINISHING: Painting the shutters with fire retardant paint of “VIPER” Brand to provide Class-1 surface spread of flame conforming to BS: 476 Part-7, IS: 12777 is desired shade including cleaning and preparation of surface.

SPECIFICATIONS OF 90 MINUTES RATED PARTIALLY INSULATED WOODEN FIRE AND SMOKE CHECK DOOR  - PRODUCT CODE WDF 8103

PARTICULARS

Providing and fixing doorframe of Seasoned hardwood / 2nd class Teakwood/ Pressed steel frame * of 120mm * 70mm section (nominal) with heat activated Intumescent fire seal strips of min 12mm * 4mm (for smoke sealing) fixed on all the three sides except the bottom. The frame being suitable for mounting 60 minutes fire resistant shutters, with one coat of anti-termite fire retardant primer. 

Providing and fixing of non-metallic, 50mm thick, asbestos free, PARTIALLY INSULATED composite Fire & Smoke check shutters of 60 minutes fire resistance rating confirming to BS: 476 part-22, IS: 3614 part II, as per prototype tested & Certified at CBRI Roorkee, duly approved by TAC (Traffic Advisory Committee) suitable for mounting on door frames as per item no.1. It comprises of two non combustible boards each 12 mm thick, sandwiching 20 mm thick Fire Resistant Filler, faced with 3mm commercial ply facing on both faces and teakwood lipping all around the shutters with heat activated Intumescent Fire Seal strip of size 12 mm * 4mm mounted in the grooves in the shutter on all sides except bottom with hinges and one coat of Anti-termite fire retardant primer.

-- SINGLE LEAF                                                                      Rs. Per Sq. Mtr.

-- DOUBLE LEAF                                                                    Rs. Per Sq. Mtr.

FINISHING: Painting the shutters with fire retardant paint of “VIPER” Brand to provide Class-1 surface spread of flame conforming to BS: 476 Part-7, IS: 12777 is desired shade including cleaning and preparation of surface.

SPECIFICATIONS OF 90 MINUTES RATED FULLY INSULATED WOODEN FIRE AND SMOKE CHECK DOOR  - PRODUCT CODE WDF 8104

PARTICULARS

Providing and fixing doorframe of Seasoned hardwood / 2nd class Teakwood/ Pressed steel frame * of 140mm * 65mm section (nominal) with heat activated Intumescent fire seal strips of size 20mm * 4mm (for smoke sealing) fixed on all the three sides except the bottom. The frame being suitable for mounting 90 minutes fire resistant shutters, with one coat of anti-termite fire retardant primer.

Providing and fixing of non-metallic, 55mm thick, asbestos free, FULLY INSULATED composite Fire & Smoke check shutters of 90 minutes fire resistance rating confirming to BS: 476 part-22, IS: 3614 part II, as per prototype tested & Certified at CBRI Roorkee, suitable for mounting on door frames as per item no.1. It comprises of two non combustible boards each 12 mm thick, sandwiching 25 mm thick Fire Resistant Filler, faced with 3mm Commercial/ Teak ply facing on both faces and Teakwood edging all around the shutters with heat activated Intumescent Fire Seal strip of size 20 mm * 4mm mounted in the grooves in the shutter on all sides except bottom with hinges and one coat of Anti-termite fire retardant primer.

-- SINGLE LEAF                                                                      Rs. Per Sq. Mtr.

-- DOUBLE LEAF                                                                    Rs. Per Sq. Mtr.

FINISHING: Painting the shutters with fire retardant paint of “VIPER” Brand to provide Class-1 surface spread of flame conforming to BS: 476 Part-7, IS: 12777 is desired shade including cleaning and preparation of surface.

 

SPECIFICATIONS OF 120 MINUTES RATED FULLY INSULATED WOODEN FIRE AND SMOKE CHECK DOOR - PRODUCT CODE WDF 4101

PARTICULARS

Providing and fixing doorframe of Seasoned hardwood / 2nd class Teakwood/ Pressed steel frame * of 140mm * 65mm section (nominal) with heat activated Intumescent fire seal strips of size 20mm * 4mm (for smoke sealing) fixed on all the three sides except the bottom. The frame being suitable for mounting 120 minutes fire resistant shutters, with one coat of anti-termite fire retardant primer.

Providing and fixing of non-metallic, 55mm thick, asbestos free, FULLY INSULATED composite Fire & Smoke check shutters of 120 minutes fire resistance rating confirming to BS: 476 part-22, IS: 3614 part II, as per prototype tested & Certified at CBRI Roorkee, suitable for mounting on door frames as per item no.1. It comprises of two non combustible boards each 12 mm thick, sandwiching 25 mm thick Fire Resistant Filler, faced with 3mm Commercial/ Teak ply facing on both faces and Teakwood edging all around the shutters with heat activated Intumescent Fire Seal strip of size 20 mm * 4mm mounted in the grooves in the shutter on all sides except bottom with hinges and one coat of Anti-termite fire retardant primer.

-- SINGLE LEAF                                                                      Rs. Per Sq. Mtr.

-- DOUBLE LEAF                                                                    Rs. Per Sq. Mtr.

FINISHING: Painting the shutters with fire retardant paint of “VIPER” Brand to provide Class-1 surface spread of flame conforming to BS: 476 Part-7, IS: 12777 is desired shade including cleaning and preparation of surface.

 


 

 

 